What factors cause Current unbalance
1. Voltage unbalance in supply side (1% volts could easily be 10% current).
2. Physical differences between individual stator coil shapes and connections causing small (but noticeable) resistance changes.
3. Unsymmetrical magnetic circuit - not as big a deal in the smaller "ring" lamination designs, unless highly saturated.
4. Lightly loaded machines will exhibit far higher unbalance than those loaded closer to the full nameplate rating (mostly due to the magnetizing current requirements and associated core/stray loss).
For quick solution measure the current in the three phases, then change the three supply terminals by shift the three terminal to rotate the motor in the same direction, and measure again the current, if the high current move with a certain phase (example: phase L1 of supply read high current in the two case above) the problem is from supply, you can then measure the voltage at motor terminal to be sure that the control circuit and cable are good.
2. Physical differences between individual stator coil shapes and connections causing small (but noticeable) resistance changes.
3. Unsymmetrical magnetic circuit - not as big a deal in the smaller "ring" lamination designs, unless highly saturated.
4. Lightly loaded machines will exhibit far higher unbalance than those loaded closer to the full nameplate rating (mostly due to the magnetizing current requirements and associated core/stray loss).
For quick solution measure the current in the three phases, then change the three supply terminals by shift the three terminal to rotate the motor in the same direction, and measure again the current, if the high current move with a certain phase (example: phase L1 of supply read high current in the two case above) the problem is from supply, you can then measure the voltage at motor terminal to be sure that the control circuit and cable are good.
I remember my very first power supply. They threw me in the deep end in 1981 building a multi-output 1 kW power supply. I was fresh from college, thought i knew everything, and consumed publications ...
Well, depending on the power rating, and on the required reliability, I believe it's very simply. The biggest problem would be to get a variable frequency drive, or other power supply to provide a 3-phase ...
Variable speed drive switches very fast which brings high dv/dt on motor. How often do we face with problems coming with VSD? How harmful is the common mode currents in windings and other parts of motor due to ...
In electric motor stop, the traditional control ways are accomplished by momentary power cutting off. But in lots of applications, it's not allowed the motor instant shutdown. For example: high-rise buildings, ...
I don't believe the interchangeable battery pack idea is workable. Who is going to own the battery packs and build the charging stations? And what happens if you get to a charging station with a nearly dead ...
Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.
Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ...
A frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ...
Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ...
Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ...
Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...
Alternative Energy field (Solar, Wind and Hydro)
Design Implications in Sub Micron Positioning
What's the alternative for a solar system?
Servo controllers of Allen Bradley K300
Looking for 4 Mw PV modules 250Wp poly EU production
Doubts on I/O Count, Smart MCC, Motor control Philosphy..
400 kV transmission line charging
In case Copper, annealed soft-drawn...
Design Implications in Sub Micron Positioning
What's the alternative for a solar system?
Servo controllers of Allen Bradley K300
Looking for 4 Mw PV modules 250Wp poly EU production
Doubts on I/O Count, Smart MCC, Motor control Philosphy..
400 kV transmission line charging
In case Copper, annealed soft-drawn...