Wiki
Home » Blog » Wiki » Difference between ICCB, MCCB and MCB

Difference between ICCB, MCCB and MCB

The aforementioned types of Circuit Breakers are used in LV System and generally based on the same operating principle.
MCB and MCCB/ICCB have a bimetal heater for overload which releases the Contact s while for short circuit the trip / electromagnet hammers itself against moving contacts. The arc created by breaking contacts is extinguished in an arc chamber. Are defined as “Thermo-magnetic “ CBs , accordingly. It is operating characteristic addressing the overload by thermal action of the bimetal strip and instantaneously dealing with short circuit occurrences by electromagnetic action.

MCB – Miniature Circuit Breaker is suitable for domestic usage. Used to protect final circuits from O/C such as Overload & Short Circuit.
i- MCB is basically made in accordance to BS 3871, is now superseded by BS EN 60898 which recognizes type B, C & D.
Type B is suitable in domestic premises.
Type C is used in commercial & industrial applications.
Type D is suitable for application where a high in-rush current is expected.
ii- MCB is of low breaking / making capacity as well as low current rating compared with MCCB/ICCB. MCBs available in different number of poles (SP, DP, TP,,).

MCCB – Molded Case Circuit Breaker & Insulated Case Circuit breaker are also current limiting devices but with high making/ breaking capacity and current ratings compared with MCB. MCCB and ICCB are almost the same and both are manufactured in accordance to NEMA AB1/AB3 to suit industrial and commercial purposes.
The advent of electronic protection increased the use of them and the scope is widened like tolerances, range of time & current adjustment. By virtue of that a good discrimination can be achieved with accuracy about ±10%.
Eventually, MCCB/ICCB has advantages in the capability of accommodating further features which can be provided as
i. RCD.
ii. Under voltage device.
iii. A shunt trip coils that enabling remote tripping.
iv. Auxiliary switches for remote monitoring and/or control.
IS THERE ANY DIFFERENCE BETWEEN MCBs, MCCBs ,ICCBs EXCEPT THEIR CURRENT CARRYING CAPACITY??
---->> by PRIYA

Post a Comment:

    
Calculate (5 * 5) =

You may also like:

When operating an AC machine on a variable frequency drive, the most common approach is to mimic the DC curves. This is done by using a constant volt/hertz ratio until a "base" speed is achieved at rated ...
In inverter regular inspection, we must cut off power before operation. Wait 4minutes (the bigger the longer, the maximum waiting time is 15 minutes) till the frequency inverter display panel LED indicator ...
For flyback & boost applications, powder cores such as Kool-mu, Xmu, etc... are usually best performing and lowest cost. Even these may need to be gapped and if CCM operation is required, a "stepped-gap" ...
There are two important different parameters as far as the disconnection/connection of Electrical utilities is concerned. - Breaking capacity. - Making Capacity.
The method of creating a die-cast rotor is as follows: 1. An assembly of steel laminations (which may or may not be grain-oriented) containing the openings for both rotor bars and ventilation (as required) is ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion