Why transformer rating is shown in KVA?
Transformers are rated in {VA, kVA, MVA etc.} due to flows of active and reactive power through transformer. In case of transformer we have active power losses as consequence of existence inside resistance of windings (primary and secondary) and existence of active losses of ferromagnetic core and other side we have reactive power losses as consequence of existence losses of magnetic flux (primary and secondary) and existence of reactive power losses of ferromagnetic core.
[VA]=sqrt(sqr[W]+sqr[VAr])
Transformer is rated in kVA by the manufacturer to inform users about the maximum power (voltage and current) that support it, the reason for not rating it in KW is that the active power (kW) is depend on the loads (lighting, machines..)
The simple answer is: It is because the kVA (or MVA) rating is only rating that matters to express a transformer's "capacity" to allow the “passage" of power. That capacity is the thermal capacity dictated by the current it can carry at a given ambient temperature, regardless of the power factor. So combined with its voltage ratings, kVA (or MVA) is the value that matters. kW rating does not matter as transformer can handle unity power factor or in other words, a transformer can handle kW equal to its kVA rating at any time.
Remember that a transformer, as the name suggests, is only a transformation device or a pass through device and not a power producing device like a generator or an UPS, where their capacity to produce real power (kW) is an independent limit from the thermal ( kVA) limit.
To take it a step further, if you have an ability to cool the transformer further, you can augment the kVA (or MVA) rating of a transformer. This would explain having multiple kVA/ MVA ratings on transformers with forced cooling aids installed on them.
If you think of it, this is not different from a cable or a conductor's capacity expression. Except that a transformer can have more than one voltage levels and different ampacities on primary and secondary, but the kVA rating remains the same on either side. So that makes kVA a more convenient way to express its thermal capacity vs. the amperes alone.
[VA]=sqrt(sqr[W]+sqr[VAr])
Transformer is rated in kVA by the manufacturer to inform users about the maximum power (voltage and current) that support it, the reason for not rating it in KW is that the active power (kW) is depend on the loads (lighting, machines..)
The simple answer is: It is because the kVA (or MVA) rating is only rating that matters to express a transformer's "capacity" to allow the “passage" of power. That capacity is the thermal capacity dictated by the current it can carry at a given ambient temperature, regardless of the power factor. So combined with its voltage ratings, kVA (or MVA) is the value that matters. kW rating does not matter as transformer can handle unity power factor or in other words, a transformer can handle kW equal to its kVA rating at any time.
Remember that a transformer, as the name suggests, is only a transformation device or a pass through device and not a power producing device like a generator or an UPS, where their capacity to produce real power (kW) is an independent limit from the thermal ( kVA) limit.
To take it a step further, if you have an ability to cool the transformer further, you can augment the kVA (or MVA) rating of a transformer. This would explain having multiple kVA/ MVA ratings on transformers with forced cooling aids installed on them.
If you think of it, this is not different from a cable or a conductor's capacity expression. Except that a transformer can have more than one voltage levels and different ampacities on primary and secondary, but the kVA rating remains the same on either side. So that makes kVA a more convenient way to express its thermal capacity vs. the amperes alone.
1: Torque boost: this function is the variable speed drive increases output voltage (mainly in low frequency) to compensate the torque loss due to voltage drop in the stator resistance, thereby improving the ...
Before you select kind of cable for your consumer, you need to calculate expected operating current of cable which depends from rated power of your consumer. After that, before you select kind of cable for ...
In speaking with many engineers over several decades, a large manufacture of large electric motors, have decided once a rotor is identified as the problem, rebarring, or any single repair is usually ...
As far as I know all variable frequency drives with vector control can also be run with just V/F control.
A drive in vector control mode has several tuning parameters to increase or decrease motor ...
I have a problem with ABB ACS800-104-0105-3 drive model, the output current reading on the VFD is always double the reading of the clamp ampere(i.e. drive reading= 40 A, clamp ampere reading=20 A), what is the ...
Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.
Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ...
A frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ...
Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ...
Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ...
Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...
PUMP SELECTION - How can i increase my NPSH margin ?
How to select the best control valve?
Does anyone know what is life cycle for solar panel?
Are there lists of motion control integrators by state?
suction pump up on land
inverters with multiple MPPT
flyback converter design
what is the permissible Resistance of earthing rod as per BS7671
How to select the best control valve?
Does anyone know what is life cycle for solar panel?
Are there lists of motion control integrators by state?
suction pump up on land
inverters with multiple MPPT
flyback converter design
what is the permissible Resistance of earthing rod as per BS7671