Change 230V to 460V for operating an Electric Motor
I have a generator of 3 hp, and it outputs 230 V, and I have a submersible Electric Pump, the motor of which is rated to operate at 460 V, Can I use a step up transformer to increase the voltage output from my generator and power the pump? What more parameters do I need to know of in this case?
Check to see if the generator has 3 phase power output. A typical home generator will provide 230 volt single phase output. You will not be able to step up to 460 volt and start a 3 phase motor with single phase. The only way at that point to generate 3 phase would be to use a VFD with single phase input capability and use the drive to generate 3 phase. You will still need to use a transformer. Variable frequency drives won't normally behave well on generator power but may for an intermittent load like a submersible pump.
Check to see if the generator has 3 phase power output. A typical home generator will provide 230 volt single phase output. You will not be able to step up to 460 volt and start a 3 phase motor with single phase. The only way at that point to generate 3 phase would be to use a VFD with single phase input capability and use the drive to generate 3 phase. You will still need to use a transformer. Variable frequency drives won't normally behave well on generator power but may for an intermittent load like a submersible pump.
The rotating electrical machines have basically three noise sources:
The ventilation system
The rolling bearings
Electromagnetic excitation
Bearings in perfect conditions ...
Well first let get one thing straight for transformers: the higher the line frequency, the lower the core (iron) losses! The core power loss are proportional to kf*B^2 approximately for any machine, dynamic or ...
The PPE (Personal Protective Equipment) requirements to work on live electrical equipment is making doing commissioning, startup, and tuning of electrical control systems awkward and cumbersome. We are at a ...
The voltage transient which occurs whenever there is a sudden change in current in an inductive device. Inductors resist a sudden current change.
V=L di/dt
In electric motors this occurs at start up when the ...
r/min: motor rotation speed unit, the number of revolutions per minute, also can be expressed in rpm.
For example: 2-pole motor 50Hz 3000 r/min, 4-pole motor 50Hz 1500 r/min
Conclusion: The motor rotation ...
Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.
Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ...
A frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ...
Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ...
Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ...
Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...
What are the top 5 things you look for in your HMI/SCADA software?
Solar and small wind Power Systems for the huge Sri Lanka and Maldives Market
solar plant
How much time do you spend investigating new SCADA software technology?
MV Induction Motor Protection
What is the significance of short circuit ratio?
VARIABLE SPEED ENGINES AND SHAFT CRITICAL SPEEDS
Electrical Machine design Using MATLAB
Solar and small wind Power Systems for the huge Sri Lanka and Maldives Market
solar plant
How much time do you spend investigating new SCADA software technology?
MV Induction Motor Protection
What is the significance of short circuit ratio?
VARIABLE SPEED ENGINES AND SHAFT CRITICAL SPEEDS
Electrical Machine design Using MATLAB