Experience
Home » Blog » Experience » Avoid voltage drop influence

Avoid voltage drop influence

My cable size and transformer size should give me maximum 3% on the worst 6% to 10%. If it is the single only equipment on the system then maybe you can tolerate 15%. If not, dip factor may affect sensitive equipment and lighting.

This is very annoying for office staff each time a machine starts lights are dimming. It does not matter what standard you quote I cannot accept 10%- 15% make precise calculation and add a 10% tolerance to avoid.

In most cases, this problem comes from cable under sizing so we have to settle with a Standard giving 15% Max.

Just recently I had to order a transformer and cable change for a project which was grossly undersized.
I have had to redesign the electrical portion of a conveyor and crushing system to bring the system design into compliance with applicable safety codes. The site was outdoor at a mine in Arizona where ambient temperatures reach 120F. The electrical calculation and design software did not include any derating of conductor sizes for cable spacing and density within cable trays, number of conductors per raceway, ambient temperature versus cable temperature rating, etc. Few of the cables had been increased in size to compensate for voltage drop between the power source and the respective motor or transformer loads.

Feeder cables to remote power distribution centers were too small, as voltage drop had not been incorporated in the initial design. The voltage drop should not be greater than 3%, as there will be other factors of alternating loads, system voltage, etc. that may result in an overall drop of 5%.

The electrical system had to be re-designed with larger cables, transformer, MCCS, etc, as none of the design software factors in the required deratings specified in the National Electric Code NFPA70 nor the Canadian Electric Code, which references the NEC.

Post a Comment:

    
Calculate (2 - 3) =

You may also like:

The trend toward lower losses in power converters is not apparent in all of the applications of power converters. It is also not apparent that the power converter solution and its losses for a given market ...
A low impedance fault is usually a bolted fault, which is a short circuit. It allows a high amount of fault current to flow, and an upstream breaker or fuse usually senses the high current and operates, ending ...
Resistance Grounding Systems have many advantages over solidly grounded systems including arc-flash hazard reduction, limiting mechanical and thermal damage associated with faults, and controlling transient ...
If you're planning to use a Soft Starter or VFD for motor starting, you need to specify the horsepower rating, voltage rating, rated frequency, the type of motor (induction wound rotor or induction squirrel ...
Soft Start and Soft Stop is especially useful with pumping fluids where torque transients often cause water hammer effects, and in some instances, failure to gradually slow the fluid down before stopping, can ...
Gozuk Service Gozuk Blog: all about electric motor control & drives industries development in energy saving applications.

Featured

Like pumps, fans consume significant electrical energy while serving several applications. In many plants, the VFDs (variable ... energy consumedA frequency inverter controls AC motor speed. The frequency inverter converts the fixed supply frequency (60 Hz) to a ... Motor starter (also known as soft starter, motor soft starter) is a electronic device integrates soft start, soft stop, ... Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the ... Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during ...

In Discussion